The 35kV high-voltage cable branching cabinet for photovoltaic power generation is equipped with lightning arresters.
35kV cable branching cabinets are widely used in wind power plants and photovoltaic power generation projects. The cabinet can be equipped with isolating switches and lightning arresters. It connects power cables to box-type substations and ring main units, serving functions such as connection, tapping, branching, or switching, providing great convenience for cable network systems.
Operating Conditions:
Ambient temperature: -30℃ to +40℃
Relative humidity: Daily average ≤95%, monthly average ≤90%
Maximum altitude: 3000 meters
Product Features (35kV with Isolating Switch):
Customizable options: Prefabricated plug-in connectors or cold/hot-shrink cable terminations.
Fully insulated, fully sealed, fully waterproof, maintenance-free, safe, and reliable.
Functional Characteristics:
Fully insulated, fully sealed, maintenance-free, ensuring personal safety.
Eco-friendly outdoor design with HV live display simplifies urban cable networks and reduces investment.
Outdoor type, dustproof, moisture-proof, flood-resistant, corrosion-resistant, highly adaptable, flexible configuration.
Compact size, aesthetically pleasing, simple installation, easy operational switching.
Can be equipped with voltage indicators, fault indicators, lightning arresters, etc.
Advanced domestic HV equipment, filling the gap for 40.5kV(35kV) switch-equipped branching cabinets.
Suitable for 35kV AC 50Hz/60Hz transmission/distribution lines; can be used in 35kV prefabricated substations.
Reduces cable runs and footprint, improves power supply reliability.
Can be equipped with GN27-40.5 isolating switches for circuit switching under voltage, no-load conditions.
Technical Parameters:
Rated Voltage: 40.5kV
Rated Operational Voltage: 35kV
Rated Current: 630A
Frequency: 50Hz
Circuit Breaker Rated Breaking Current: 20kA
Rated Short-Time Withstand Current: 20kA (Incoming & Main Bus) / 20kA (Outgoing)
Rated Short-Time Current Duration: 3s
Rated Peak Withstand Current: 50kA (Incoming & Main Bus) / 50kA (Outgoing)
Circuit Breaker Rated Breaking Operations: 20 times
Insulation Level:
1min power-frequency withstand voltage: 42kV (ground) / 48kV (break)
Lightning impulse withstand voltage: 95kV (ground) / 110kV (break)
Load Switch Breaking Capacity:
Normal load current: 630A
Earth fault current: 95A
No-load current: 30A
Mechanical Life:
Circuit Breaker: 10,000 operations
Load Switch: 2,000 operations
Manual operating mechanism
Operating Times:
Circuit Breaker Closing: 0.2s
Circuit Breaker Opening: 0.06s
Close-Open Time: 0.002s
Circuit Breaker Bounce Time: 0.002s
Clear open/close position indication required.
Main System Configuration: BIBI
Space and interfaces reserved for FTU unit.
Cabinet Structure & Features:
Enclosure made of imported aluminum-zinc coated steel or cold-rolled steel.
Reliable “five-prevention” interlock; HV live display.
Protection rating ≥ IP3X.
Wiring diagram on each cabinet door.
Concealed lock on enclosure.
Key Features:
Outdoor/indoor use, fully sealed, “five-prevention” safety, maintenance-free.
Eco-friendly with HV display, simplifies networks, saves investment.
Weather-resistant, flexible configuration for various wiring needs.
Compact, aesthetically pleasing, easy installation/operation, flexible protection.
Small footprint, low height, blends with environment, flexible wiring.
Operating Environment:
Location: Outdoor
Seismic Intensity: 8 degrees
Altitude: ≤1000m
Weather Conditions:
Ambient temperature: -10℃ to +45℃
Daily temperature variation: 30℃
Wind speed: 35m/s (10m height, 15-year return, 10-min avg)
Solar radiation: 0.1W/cm², 0.5m/s wind
Relative humidity: Daily avg 95%, monthly avg 90% (25℃)
Pollution level: Grade IV
Ice thickness: 0-30mm
System Conditions:
Rated Frequency: 50Hz
Nominal Voltage: 35kV
Operational Voltage: 40.5kV
Rated Power-Frequency Voltage (conductor to earth/screen): 26kV
Technical Requirements:
Basic Parameters:
| Item | Unit | Technical Requirement |
|---|---|---|
| Rated Voltage | kV | 35 |
| Rated Frequency | Hz | 50 |
| Rated Current | A | 630 |
| Rated Insulation Level | kV | 40.5 |
| Rated Short-Duration Power-Frequency Withstand Voltage (rms) | kV | 117 |
| Rated Lightning Impulse Withstand Voltage (peak) | kV | 200 |
| Protection Level | – | ≥ IP54 |
| Cable Accessories | ||
| Impulse Withstand Voltage | kV | 200kV, ± polarity 10 times each, no breakdown/flashover |
| DC Withstand Voltage | kV | 104kV (negative polarity), 15min, no breakdown/flashover |
| Partial Discharge | pC | ≤10 @ 45kV |
Design & Structure Requirements:
Function: For interconnecting cable lines and connecting to branch lines outdoors, enabling power distribution. Uses TMY copper busbars, composite insulation. Safe clearance ≥400mm.
Safety Design: Ensures safe operation, inspection, maintenance, voltage status indication, phasing, cable grounding, testing, and static discharge.
Enclosure:
Material: ≥3.0mm stainless steel or cold-rolled steel, robust for handling.
Coating: Electrostatic spray ≥150μm, uniform, adherent, color-fast for 15+ years.
Color: Coordinates with environment, clear warning signs.
Doors: Open >90°, with stops, seals, handles, concealed latches, rain/rust proof hinges, locks, external lock points.
Ventilation: Natural vents to reduce condensation.
Internal Insulation Barrier: With safety warnings.
Roof: Rain shield.
Diagram: Internal schematic with operating instructions.
Lifting: 4 lifting rings.
Waterproof: Protection rating ≥ IP54.
Earthing:
Complies with DL/T 621-1997. All exposed metal earthed.
Earthing conductor withstands rated short-time/peak current.
Dedicated earthing conductor with ≥2 visible connection points, clearly marked.
Insulation:
Composite insulation. Safe clearance ≥400mm.
Insulators: Flame-retardant, creepage distance >16mm/kV, support insulator creepage ≥648mm.